►Steam Traps | Air Vent - 1" (Page 1)


Air Vent
Size: 1"

Typical applications:
Liquid Systems

Main Features:
Any system filled with water or other liquids will not function correctly unless air and other incondensable gases are removed. EYVAZ Air and Gas Eliminators prevent air and other gases from retarding circulation, causing corrosion and noise, inhibiting the filling of systems or priming of pumps. They are available in a variety of designs for hot water, cold water and many other liquid systems. EYVAZ Air and Gas Eliminators can easily be dismantled for servicing, usually without disturbing pipe connections.

Installation:
The steam trap must be fitted with the float arm in horizontal plane so that the float rises and falls vertically in the body.

Technical Data
Operating Conditions Cast Iron Body
Max. Allowable pressure PMA (bar) 25
Max. Allowable temperature TMA (°C) 200
Max. Operating pressure PMO (bar) 16
Max. Differential pressure PMD (bar) 6
Max. Operating temperature TMO (°C) 250
 
Sizes, Weights & Connections Screwed Flanged
Size (mm) 1 25
Weight (Kg) 6.8 8.3
Connection NPT acc. to ANSI BI 20.1 BSP acc. to BS 21 DIN 2533

 

 