►Control Valves | Temperature Control Valve, Type 4 (Page 2)

Technical Data.
Pressures stated in bar (gauge). The permissible pressures and differential pressures specified are limited by the pressure, temperature diagram and the nominal pressure ratings acc. to DIN 2401.

Type 4 control valve

PN 16 / 40

Kvs - values and permissible differential pressures ∆p)
Standard version  DN 15 20 25 32 40 50 65 80 100
Kvs 3.2 5 8 12.5 20 32 50 80 125
Differential pressure  ∆p 25 25 25 25 25 25 16 16 10
Special version  DN 15...25 25 32 40 50 65 80 100
Kvs 0.16/0.4/1/2.5/3.2 5 5 8 12.5 20 32 50
Differential pressure  ∆p 25 16 10
Leakage rate

≤0.05 % of kvs valve

Permissible temperature of the valve See Pressure-Temperature diagram
Type 2231-2241 control thermostat Size 15-150
Set point range -10...+90 °C, 20...120 °C, 50...150 °C
Permissible ambient temperature at the set point adjustment cylinder -40 to +80 °C
Permissible excess temperature at the sensor 75 °C Above the actual set point
Permissible PN 40
Length of capillary tube 3 m (special version : 5, 10 or 15 m)

Material (WN = DIN Material Number)
Type 4 control valve
Nominal size DN 15 to DN 100
Nominal pressure PN 16  PN 25 / 40
Valve body and connection flange Cast Iron
GG-25 WN
0.6025
Cast Iron
GS-C25
WN 1.0619
Stainless
Steel
WN 1.4581
Seat / plug  Stainless Steel WN 1.4059 / WN 1.4301
Plug stem /spring WN 1.4301
Bellows blousing  St 35.8(WN 1.0305)
Balancing bellows stainless steel WN 1.4541
Body gasket Graphite on metal core
Type Thermostat 2231-2241
Operating element Brass, Nickel - Plated
Sensor Brass, Nickel - Plated
Capillary tube Copper, Nickel - Plated
Thermowell with treaded nipple Brass, Nickel - Plated
(special version stainless steel) 

- Flow Diagram of Water
The values shown are valid for a fully-opened control valve

 

Control valve sizing for other media according to DINIIEC 534,parts 2-1 and 2-2, with following terms:
FL = 0.95 and XT = 0.75

 

 

 

Accessories
If the operating conditions affect the reliability of the operating element , an extension piece and I or a distance piece is mounted between the control valve and the operating element.

The extension piece is needed for temperature above 150 °C or 220 °C respectively (See Pressure-Temperature Diagram).

 

 