►Control Valves | Pressure Reducing Valve, Type PRV (Page 2)


Self-Operated Pressure Controller
Pressure Reducing Valve Type PRV

Installation
The valve should be installed in a horizontal pipeline with the direction of flow as indicated by the arrow on the valve body.

Steam and Compressed Air Capacities

How to use the chart by an example:
The curved lines labeled 2, 3, 4, 5 etc., represent upstream pressures. Downstream pressures are read along the vertical line on the left 1 hand side of the chart.

Required, a reducing valve to pass 120 kg / h reducing from 8 to 6 bar. From the downstream pressure of 6 bar on the left hand side of the chart extend out horizontally until the line meets the curved 8 bar upstream line. At this point read vertically (according to fig)

Sizes and Pipe Connections
1/2", 3/4", 1" Screwed BSP or NPT.

Note: Before carrying out any work on the valve, make sure that it is fully isolated.

To fit new valve and seat or to clean strainer screen
Release adjustment spring pressure by turning Adjustment knob (2) fully anti-clockwise. Remove spring housing by undoing 4 spring housing bolts (7). Lift out bellows assembly. Using 32mm A/F spanner, Unscrew seat (11) and remove valve, return spring, strainer screen push rod and guide bush. Clean strainer screen or replace with new valve and seat assembly. Re-assemble in reverse order, using new gaskets, ensuring that components and seating faces are clean: Tighten seat to 108/132 Nm. Tighten spring housing bolts to 8/24 Nm.

How to Order
Always order spares by using the description given in the column headed Available Spare and stating the size, rate and downstream&upstream pressure range of the valve.
 

 Back Next Top
 

Home | About Us | Products | Request Form | Contact
Copyright 2003 Eyvaz Technic Co. All rights reserved.